XBD-SLOW
XBD-SLOW — Horizontal Split-Case Double-Suction Fire Pump
Description
A new generation of single-stage double-suction and two-stage double-suction XBD-SLOW fire pumps with a horizontal split casing. A wide and well-considered range of sizes simplifies selection for various fire protection conditions.
Design variants: single-stage double-suction horizontal with a mid-port; two-stage double-suction horizontal with a mid-port.
Technical Specifications
| Flow range | 25~325 L/s |
|---|---|
| Pressure range | 0.3~2.5 MPa |
| Rotation speed | 1490 rpm, 2980 rpm |
| Voltage | 380 V, 6 kV, 10 kV |
| Liquid temperature | ≤80°C |
| Ambient temperature | typically ≤40°C |
| Maximum allowable inlet pressure | 0.4 MPa |
| Suction and discharge diameters | DN80~DN400 mm (GB/T 17241.6 flange) |
| Medium | clean water or mildly corrosive liquids without solid particles |
| Pressure, p | ≤25 bar |
Applications
- Water supply for fixed fire protection systems in industrial and civil buildings
- Hydrant systems, sprinklers, and water mist
- Standalone and combined fire protection / domestic water supply
- Water supply for buildings, municipalities, industrial and mine facilities, boiler feed
Need advice on selecting equipment?
LCPumps specialists will help you select a pump or system for your parameters — flow rate, head, medium and operating mode.
Request a Consultation